CADR and Ozone Limits for Portable Air Cleaners

14 hours ago
10 min read

Compliance reviewed by Onur Oncer, SDVOSB Materials compliance lead.


What Does a CADR Rating Actually Tell a Federal Buyer?


Clean Air Delivery Rate is the volume of contaminant-free air a portable air cleaner delivers per minute, measured as a complete system. ANSI/AHAM AC-1-2020 defines CADR in Section 3.14 as the delivery of contaminant free air, within the defined particle size range, expressed in cubic feet per minute. SDVOSB Materials Technology & Supply LLC specifies these units through its LabTECH Air division, alongside the fixed equipment covered in our fume hood and air safety procurement guide.


The number is a subtraction, which is the part most specifications miss. AC-1-2020 computes CADR by taking the rate at which particles disappear while the cleaner runs, subtracting the rate at which they would have settled out anyway, and multiplying by the volume of the test chamber. What is left is the air the machine itself cleaned. That construction is why CADR cannot be read off a fan curve. Section 3.14 states that CADR values are always the measurement of an air cleaner performance as a complete system, and that they have no linear relationship to air movement per se or to the characteristics of any particular particle removal methodology. A 400 cfm fan bolted to a poor filter does not produce a 400 cfm CADR. Buyers who treat the two as interchangeable overbuy on noise and underbuy on cleaning.


Which Three Particle Sizes Does ANSI/AHAM AC-1-2020 Test?


AC-1-2020 produces three separate CADR numbers, not one, because it runs three different test contaminants across three particle size bands. A unit that performs well on pollen can perform poorly on smoke. SDVOSB Materials reads all three before recommending a unit for a federal space.


  • Cigarette smoke: particle sizes detected from 0.10 to 1.0 micrometres, per Section 3.3.1. This is the smallest and hardest band, and the one that drives the room size rating.

  • Air cleaner fine fraction test dust: 0.5 to 3.0 micrometres, per Section 3.3.3.

  • Paper Mulberry Pollen, non-defatted: 5 to 11 micrometres including fragments, the coarsest band.


Section 8.6 of AC-1-2020 ties the familiar coverage-area claim to the smoke number alone: suggested room size in square feet equals the cigarette smoke CADR multiplied by 1.55. That figure assumes a mixing factor of 1.0, an air exchange rate of one per hour, and an eight-foot ceiling. Federal rooms with higher ceilings, heavier outside air loads or poor mixing will not behave like the model, so the coverage number on a box is a starting point rather than a design value.


What CADR Range Is the AC-1 Test Method Valid Within?


AC-1-2020 states its own limits of measurability, and they are narrower than most buyers assume. Section 2 of the standard sets a floor of 10 cfm for dust, 10 cfm for cigarette smoke and 25 cfm for pollen, because below those values a CADR cannot be distinguished from zero at a 95 percent confidence limit. The ceiling is 600 cfm for dust and smoke and 450 cfm for pollen.


The precision statement matters just as much when two bids are close. AC-1-2020 reports, for a zero-CADR air cleaner, two standard deviation limits of plus or minus 10 cfm for dust, plus or minus 10 cfm for smoke and plus or minus 25 cfm for pollen. SDVOSB Materials treats that as the practical floor on meaningful separation between bids, so a 240 cfm unit and a 250 cfm unit are not worth distinguishing in a specification. All of it is produced in one fixed room: Annex A of AC-1-2020 specifies a chamber of 10.5 by 12 by 8 feet, which is 1,008 cubic feet. The rating describes behaviour in that box, not in a 40-bed dormitory or an open laboratory.


Where Does Federal Regulation Reference CADR?


The U.S. Department of Energy incorporated AC-1-2020 by reference at 10 CFR 430.3, which lists ANSI/AHAM AC-1-2020, Method for Measuring Performance of Portable Household Electric Room Air Cleaners, ANSI-approved December 14, 2020, including the AHAM Standard Interpretation dated September 19, 2022. That incorporation is approved for Appendix FF to Subpart B of Part 430.


Appendix FF, the Uniform Test Method for Measuring the Energy Consumption of Air Cleaners, applies only enumerated pieces of the standard. Section 0.1 of Appendix FF adopts Sections 4.2 through 4.6, Sections 5 through 7, Section 8.1, Annex A, Annex I and the AHAM Standard Interpretation. Its scope reaches a conventional room air cleaner with smoke CADR and dust CADR between 10 and 600 cfm, inclusive.


Two honest caveats belong in any specification SDVOSB Materials writes against this. Appendix FF is an energy test procedure, so it governs how energy use and CADR are measured rather than setting a minimum cleaning performance. Its own prefatory note ties mandatory use to the compliance date of any energy conservation standards for air cleaners, and as of October 12, 2026 no such standard is in force for this product. The title of AC-1-2020 also says household, and 10 CFR 430.2 defines a conventional room air cleaner as a portable or wall mounted unit that plugs into an outlet, operates with a fan, and contains means to remove, destroy or deactivate particulates. Nothing in that scope certifies a unit for a BSL containment suite.


Does ANSI/AHAM AC-1-2020 Address Ozone at All?


No. AC-1-2020 does not test for ozone, does not set an ozone limit, and does not mention ozone anywhere in the document. SDVOSB Materials verified this against the full text of the standard on October 12, 2026. A CADR rating, however high, is silent on whether the unit puts ozone into the room.


The standard is explicit about what it covers. Section 2 scopes it to the relative reduction of particulate matter suspended in the air of a test chamber, plus operating and standby power. For safety it defers outward: Section 12 recommends that air cleaners meet the relevant requirements of UL 867, the Standard for Electrostatic Air Cleaners, and UL 507, the Standard for Fans. This gap is the specification error LabTECH Air watches for on air cleaner buys. A procurement writes a smoke CADR minimum, a vendor supplies an ionizing or electrostatic unit that meets it, and nothing in the solicitation ever asked what the ionizer emits. The ozone question has to be specified separately, against a different authority.


How Do You Confirm a Unit Emits No Ozone Into an Occupied Room?


Specify certification under the California Air Resources Board air cleaner regulation, codified at Title 17 of the California Code of Regulations, Sections 94800 through 94810. Section 94802 prohibits manufacturing for use in California, selling, supplying, offering for sale or introducing into commerce any indoor air cleaning device intended for use in occupied spaces unless ARB has certified it to produce an ozone emission concentration not exceeding 0.050 ppm, and Section 94803 excludes devices marketed and labeled solely for industrial use, together with in-duct systems integrated into a central heating, air conditioning or ventilating system, from the article entirely. The rule reaches medical and non-medical devices alike. No federal program certifies portable air cleaners for ozone before sale; the closest federal rule, FDA's 21 CFR 801.415(c)(1), treats an ozone-generating device as adulterated or misbranded if it generates ozone above 0.05 ppm by volume of air circulating through the device, or causes accumulation above 0.05 ppm in enclosed spaces intended to be occupied for extended periods. SDVOSB Materials Technology & Supply LLC therefore writes the ARB 0.050 ppm ceiling into federal specifications outside California as a buyer requirement rather than an inherited legal obligation.


The test behind that number is not CADR. Section 94805(c) states that ozone emissions will be determined using Section 37 of ANSI/UL Standard 867, which the regulation incorporates at the Fourth Edition published December 21, 2007. Section 94805(d) requires the testing laboratory to be recognized as a Nationally Recognized Testing Laboratory by OSHA, and it further requires that the lab performing the UL 867 Section 37 ozone test has passed an ARB audit of its ability to run that procedure.


The cleanest answer for an occupied federal room is to remove the emission mechanism rather than measure it. Section 94804(b) of the CARB rule exempts devices using only mechanical filtration from ozone emission testing, based on their known de minimis ozone emissions, subject to the ARB Executive Officer verifying design documentation. A HEPA-and-fan unit with no ionizer, no ultraviolet lamp and no plasma stage has nothing to emit. SDVOSB Materials Technology & Supply LLC recommends that route wherever the room is continuously occupied.


Where a buyer wants a margin below the regulatory ceiling, UL 2998, the Environmental Claim Validation Procedure for Zero Ozone Emissions from Air Cleaners, which UL designates ULE 2998 in its current program materials, validates emissions below 0.005 ppm, which UL describes as the quantifiable limit of detection and one tenth of the 0.050 ppm regulatory requirement. UL's published program description, which SDVOSB Materials verified on October 12, 2026, states that validated products are retested at least every three years with surveillance audits in the intervening years.


What Should the Specification Language Require?


SDVOSB Materials writes air cleaner specifications in this order, because each line closes a gap the previous one leaves open.


  1. State the required smoke CADR in cfm, tested per ANSI/AHAM AC-1-2020, and require the test report rather than a marketing figure. Smoke is the governing band.

  2. Keep the required value inside the 10 to 600 cfm range ANSI/AHAM AC-1-2020 is valid within, and do not write a tolerance tighter than the plus or minus 10 cfm precision AC-1-2020 itself reports.

  3. Require either ARB certification under 17 CCR 94802 to the 0.050 ppm ozone limit, or documentation qualifying the unit for the mechanical-filtration-only exemption at 17 CCR 94804(b).

  4. Where the room is continuously occupied, prohibit ionization, ultraviolet and plasma stages outright instead of relying on an emission threshold.

  5. State the actual room volume and ceiling height, and treat the ANSI/AHAM AC-1-2020 coverage figure as the reference model it is rather than a guarantee.

  6. Specify filter replacement intervals, filter cost and availability over the service life, since a unit whose filters are discontinued in year three is a disposal problem.


Filter media grade is a separate question from delivered performance, and the two get conflated constantly. A MERV or HEPA grade describes the medium; CADR describes what the assembled machine delivers into the room. SDVOSB Materials' breakdown of MERV, ISO 16890 and HEPA filter ratings compared covers the filter media; CADR and the ozone question cover the assembled unit.


How Does SDVOSB Materials Support Federal Air Cleaner Procurement?


LabTECH Air is the air safety division of SDVOSB Materials Technology & Supply LLC, supplying portable air purification systems, portable fentanyl and opioid fume hoods, and laboratory safety enclosures to federal agencies, state departments of correction and academic research facilities. Where a room needs engineered containment instead of a portable unit, the division applies the same specification discipline to fixed equipment.


Scope matters when choosing between a portable cleaner and fixed equipment. A portable unit recirculates room air and never substitutes for a hood that captures at the source, which is why ASHRAE 110 containment testing and biosafety cabinet classes compared for federal labs sit alongside this guidance in the LabTECH Environments laboratory division.


SDVOSB Materials Technology & Supply LLC is certified under SBA's Service-Disabled Veteran-Owned Small Business program and is a certified HUBZone and Small Disadvantaged Business, with a New York State SDVOB certification under Control Number 171538. The company holds TIPS cooperative contract 260601 (Consulting and Other Related Services). It does not hold its own GSA Schedule; GSA orders are filled through GSA-registered partner vendors.


Frequently Asked Questions


Is a higher CADR always better for a federal room?


No. CADR scales with room volume, and ANSI/AHAM AC-1-2020 reports a precision of plus or minus 10 cfm for smoke and dust, so small differences between bids are test noise. Oversizing adds noise and energy cost. SDVOSB Materials matches the smoke CADR to the actual room volume and air change requirement.


Can a portable air cleaner replace a fume hood?


No. A portable air cleaner recirculates room air and removes particulate matter. A fume hood captures contaminants at the source and exhausts them. ANSI/AHAM AC-1-2020 tests particulate removal only and does not address vapours, gases or containment, so the two are not interchangeable. SDVOSB Materials specifies portable cleaners and engineered containment separately.


Does a HEPA filter mean the unit emits no ozone?


Only if the unit is mechanical filtration alone. Ozone comes from ionizers, ultraviolet lamps and plasma stages, not from filter media. California's rule at 17 CCR 94804(b) exempts mechanical-filtration-only devices from ozone testing based on their known de minimis emissions. A HEPA unit with an added ionizer is not exempt. SDVOSB Materials specifies mechanical-filtration-only units for continuously occupied rooms.


What ozone limit applies to an air cleaner in an occupied space?


No federal rule requires ARB certification outside California. Under 17 CCR 94802, an indoor air cleaning device sold or supplied in California for use in occupied spaces must be certified by the California Air Resources Board to an ozone concentration not exceeding 0.050 ppm, measured per Section 37 of ANSI/UL 867. Federal buyers elsewhere specify that 0.050 ppm figure.


Does the federal government require a minimum CADR?


Not currently. The Department of Energy incorporated ANSI/AHAM AC-1-2020 at 10 CFR 430.3 for Appendix FF to Subpart B of Part 430, which is a test procedure for measuring energy consumption. It standardizes how CADR and energy use are measured. It does not set a minimum cleaning performance for portable air cleaners.


Why does AC-1-2020 report three different CADR numbers?


Because it uses three test contaminants across three particle bands: cigarette smoke at 0.10 to 1.0 micrometres, fine fraction test dust at 0.5 to 3.0 micrometres, and Paper Mulberry Pollen at 5 to 11 micrometres. Removal efficiency varies with particle size, so a single figure would hide performance gaps at the smallest sizes.


Does the household scope of AC-1-2020 disqualify it for federal use?


No, but it limits what the rating proves. ANSI/AHAM AC-1-2020 is written for portable household electric room air cleaners and measures performance in a fixed 1,008 cubic foot chamber. SDVOSB Materials treats it as a valid comparative benchmark between units, not a containment certification, and does not let it qualify equipment for laboratory or clinical containment duty.


Specify Air Cleaning Equipment With Confidence


Need to source portable air cleaning or laboratory air safety equipment for a federal, state, or commercial contract? Email LabTECH@SDVOSBmaterials.com or call (917) 216-9400, or reach the team through our contact page. SDVOSB Materials will review your room conditions and return a quote-ready specification.


ANSI/AHAM AC-1-2020, 10 CFR Part 430 Appendix FF and the CARB air cleaner regulation were each verified against primary source text on October 12, 2026. UEI K39HBMPLN4B3 | CAGE 7YX60 | EIN 82-2895228. Registered active on SAM.gov.


 
 
 

Comments


CALL US

Tel: 239 710-1772  |  917 216-9400

EMAIL US

OUR LOCATIONS

Florida

New York

DC

Texas

​

OVER 35 YEARS OF TEAM EXPERIENCE

Our staff experience spans 35 years with projects ranging from $70,000 to $70,000,000 in consulting, training, delivery and technology integration, and as a part of large construction projects from Boston to San Diego and Fairbanks to Miami.

SDVOSB Materials Technology Supply LLC veteran owned small business meeting US Congress federal contracting advocacy Washingt
Disability IN supplier diversity certified vendor SDVOSB Materials Technology Supply LLC federal contractor HUBZone SDVOSB
IFMA International Facility Management Association Awards of Excellence winner SDVOSB Materials Technology Supply LLC